The 9909 ATS may be installed on fixed roof, internal or external floating roof storage tanks and pressurized tanks, such as spheres and bullets, up to a maximum working pressure of 50 psi (344 kPa).

In-Service and Out-of- Service Installations
Varec recommends fixing/weighing the end of the averaging bulb to reduce its movement in the tank to provide more accurate readings. For in-service installations, a weight (3" in diameter)may be attached to the bottom of the averaging bulb using a 9/32" (7 mm) diameter connector. For out-of-service installations, this connector may also be used to attach to a bracket that is welded to the bottom of the tank.

Standpipes and Thermowells
Floating roof tanks may utilize a perforated standpipe to house the 9909 ATS. If a thermowell is to be used with the 9909 ATS, Varec suggests the use of a 2" (51 mm) schedule 40 thermowell. A non-perforated thermowell is generally oil-filled to improve thermal response to product temperature changes.

Mounting the 9909 ATS
Two 4 " (100 mm) diameter MSS flanges with gaskets are installed, one on each side of the tank roof. The averaging bulb ¾ " (19 mm) threaded tube is then screwed into the MSS flange. This method requires access to the inside of the tank. An alternate method is to order the unit with an ANSI flange, which are available up to 4" (100 mm). The standard lead length of a flange is 4.9 ft (1.5 m); please consult the factory for any non-standard lead lengths. For use with floating roof tanks, an additional nylon bush may also be required.