9909 ATS - Calculate accurate liquid volumes to API standards by intergating an average temperature sensor into an inventory system

9909 Average Temperature Sensors

The 9909 Average Temperature Sensor (ATS) is a multiple element resistance temperature device designed to provide the average product temperature in large bulk liquid storage tanks.

The 9909 ATS provides an accurate means of measuring the temperature of the product in accordance with API 2543 standard. A combined level and temperature instrumentation solution improves management of your inventory, such as crude oils, fuel oils, diesel fuels, gasolines and liquid
gases. Overall efficiency can be increased, whether the facility is a refinery, chemical plant tank farm or distribution terminal.

Spot temperature Measurment

Operation

The sensor consists of between six and 10 graduated lengths of loop wound resistance elements housed in a flexible 316 Stainless Steel or Monel sheath. Each copper element, regardless of length, has a resistance of 100 Ohms at +77 °F (+25 °C). Each element measures resistance as it varies with the change in product temperature. The longest totally submerged element gives the best average temperature and is selected by the connected temperature transmitter or converter. As the temperature transmitter needs to know the product level in order to select the correct element, Varec recommends the 9909 ATS as one part of an overall inventory management system.

The 9909 ATS may be installed on fixed roof, internal or external floating roof storage tanks and pressurized tanks, such as spheres and bullets, up to a maximum working pressure of 50 psi (344 kPa).

In-Service and Out-of- Service Installations

Varec recommends fixing/weighing the end of the averaging bulb to reduce its movement in the tank in order to provide more accurate readings. For in-service installations, a weight (3" in diameter)may be attached to the bottom of the averaging bulb using a 9/32" (7 mm) diameter connector. For out-of-service installations, this connector may also be used to attach to a bracket that is welded to the bottom of the tank.

Standpipes and Thermowells

Floating roof tanks may utilize a perforated standpipe to house the 9909 ATS. If a thermowell is to be used with the 9909 ATS, Varec suggests the use of a 2" (51 mm) schedule 40 thermowell. A non-perforated thermowell is generally oil-filled to improve thermal response to product temperature changes.

Mounting the 9909 ATS

Two 4 " (100 mm) diameter MSS flanges with gaskets are installed, one on each side of the tank roof. The averaging bulb ¾ " (19 mm) threaded tube is then screwed into the MSS flange. This method requires access to the inside of the tank. An alternate method is to order the unit with an ANSI flange, which is available up to 4" (100 mm). The standard lead length of a flange is 4.9 ft (1.5 m); please consult the factory for any non-standard lead lengths. For use with floating roof tanks, an additional nylon bush may also be required to ensure the floating roof moves seamlessly along the temperature probe.

Product Options