Search

8130 Remote Terminal Unit

The 8130 Remote Terminal Unit (RTU) collects and transmits data from field instruments to a central system, such as FuelsManager®, host DCS or PLCs. All information obtained can be used for inventory, alarm, control and automation.

Technical Specifications | Order Codes | Interface Modules | Accessories | Documents & Downloads

8130 RTU
Functionality

Unparalleled capabilities from modular hardware/software architecture

Application

Ideal for tank gauging, control and automation at tank farms, terminals and refineries

Integration

Reduces cost by integrating all analog, digital and serial data into one system

Servicing

ViewRTU software tool for remote configuration, programming and reporting

Meets API and is ATEX approved

Modular Communications

The 8130 RTU supports up to four interface modules that can interface to virtually any tank gauge on the market. With over 20 modules available, it is possible to integrate float and tape transmitters, HTG, servo, magnetostrictive and radar gauges from different manufacturers - all using a single device.

Control and Automation

A full range of I/O interfaces is available for the 8130 RTU, offering connectivity to virtually every type of signal encountered in industrial environments. Analog, digital and serial data inputs and outputs support simplifies integration and increases control and automation possibilities.

Tank Installation

Configuration and Support

The 8130 RTU allows remote configuration of your tank gauges, which means less on-tank activities, resulting in less personnel risk. The gauge configuration data can then be exported to other applications, such as Microsoft Excel® or Access®; thus documenting all tank gauge equipment.

Built-in Software

Software "blocks" built into the device provide a broad range of complex, but commonly needed functions, such as analog scaling, flow measurement and totalization, digital alarm handling, and pump/valve acquisition and control.

Technical Specifications

Specification
Power Supply - 110–120 V AC or 200–240 V AC @ 50/60 Hz or 18–36 V DC
Consumption - 50 VA max @ 110/220 VAC (500 mA), 20 VA max @ 24 VDC
Operating Temperature Range ‐40 to +158 °F (‐40 to +70 °C)
Approvals FM ‐ Class I, Division 2, Groups A, B, C & D T3C (with optional NEMA 4 enclosure required)
CSA ‐ Class I, Division 2, Groups A, B, C & D (with optional NEMA 4 enclosure required)

For complete technical specifications, download the technical document or product manual.

Order Codes

The following options are available for this product.


  • 110...120 V AC 50/60 Hz
  • 220...240 V AC 50/60 Hz
  • 18...36 V DC
  • None
  • TSU Emulation ‐ for connection to Varec TankView systems
  • CIU Emulation ‐ emulates Enraf model 858 CIU interface
  • None
  • Varec Matrix Communication ‐ interfaces to Varec Matrix devices (1600/1700) require 8210, 8201 & 8204 Interface Modules
  • MODBUS Master Communication*
  • CIU communication ‐ interfaces to existing Enraf 858 CIU devices*
  • Veeder Root (TLS 350) Communication*
  • Hectronic OptiLevel Communication*

  • Note! * Using RTU motherboard communications ports

  • None
  • Hybrid tank calculations
  • Hydrostatic tank calculations
  • None
  • Embedded tank strapping tables
  • Floating Roof Tank with Floatwell
  • Tank Top Mounting
  • Bolted Tank
  • Cone Roof Tank with Pan (No Floatwell)
  • Floating Roof Tank (No Floatwell
  • For use in non‐hazardous areas
  • FM ‐ Class I, Division 2, Groups A, B, C & D T3C (with optional NEMA 4 enclosure required)
  • CSA ‐ Class I, Division 2, Groups A, B, C & D (with optional NEMA 4 enclosure required)

Interface Modules

The following interface modules are available for this product.


Interface Module 8201
  • 16 digital I/O channels
  • 24 VDC, 120 or 240 VAC
  • Channels individually configurable for input or output
  • Dedicated status LED
  • Dedicated fuse for output modules only
  • Requires two I/O expansion module slots
Interface Module 8203
  • Dual high-speed communications channels
  • Optically isolated
  • Up to 32 devices per channel
  • Communications with instruments using Rackbus, MODBUS, DDA, or Petrosense Probe protocols
  • Requires one I/O expansion module slot
Interface Module 8204
  • Isolated analog (4-20 mA), Thermocouple, RTD inputs, high speed pulse accumulation or digital I/O channels
  • 24 VDC, 120 or 240 VAC operation
  • Individually configurable for input or output
  • Dedicated status LED/fuses
  • Requires one I/O expansion module slot
Interface Module 8205
  • 12 bit accuracy A/D with common-mode noise rejection
  • Dedicated fused 24V line for each channel
  • Throughput accuracy (field to database) = ±0.012%.
  • Each channel individually configurable for; 4-20 mA loop powered input, 4-20 mA self powered, voltage input
  • Requires two I/O expansion module slots
Interface Module 8207
  • 16 Bit accuracy D/A converter
  • Current or voltage level output (0-24 mA, 0-20 mA, 4-20 mA & 0-5V)
  • 8 channels
  • Requires one I/O expansion module slot
Interface Module 8208
  • Dual high-speed communications channels
  • Optically isolated
  • Up to 32 devices per channel
  • Communications using TIWAY or CIM protocol
  • Requires one I/O expansion module slot
Interface Module 8210
  • Supports up to 50 tanks
  • Communicates using Mark/Space protocol
  • Interfaces to the Varec 1900 and compatible tank gauge transmitters
  • Requires one I/O expansion module slot
Interface Module 8211
  • 20 mA current loop
  • Up to 15 devices per channel
  • Two channels
  • Communicates using GPE or Whessoe Bus protocol
  • Requires one I/O expansion module slot
Interface Module 8212
  • Saab (Emmerson) TRL/2 Bus
  • Up to 16 Saab Radar Tank Gauges per channel
  • Two channels
  • Requires one I/O expansion module slot
Interface Module 8214
  • Transformer isolated
  • Up to 10 tanks per channel
  • Two channels
  • Communications with Enraf tank gauges
  • Requires one I/O expansion module slot
Interface Module 8215
  • Supports up to 50 tanks
  • Communicates using L&J Tankway protocol
  • Interfaces to L&J Tankway compatible tank gauge transmitters
  • Requires one I/O expansion module slot
Interface Module 8216
  • Supports up to 128 tanks
  • Communicates with LON Series 3500 TCU
  • 78 Kbps twisted pair LON interface
  • Requires one I/O expansion module slot
Interface Module 8217
  • Dual high-speed communications channels
  • RS-232 communications
  • Communicates with L&J Model 8100
  • Communicates with Veeder Root TLS-350
  • Communicates with Universal Sensors & Devices CATLAS
  • Communicates with Enraf CIU
  • Communicates with MODBUS devices
  • Requires one I/O expansion module slot