8130 Remote Terminal Unit
The 8130 Remote Terminal Unit (RTU) supports up to four individual interface modules that can interface to virtually any tank gauge on the market. Each interface module will scan all the connected gauges for measured data such as: level, temperature, density, water level and alarms.
The 8130 RTU also connects to most types of sensors or actuators on your site and to PLCs and DCS computers. All information obtained can be uploaded to the host system for inventory, alarm and control purposes.
- Easily expandable through the use of plug-in modules; reduces cost by integrating all analog, digital and serial data inputs and outputs
- Multiple host ports; adapt to your needs and redundancy requirements
- Support of multiple tank gauge protocols; connect your existing equipment at less cost
- Digital and analog I/O connectivity; allows simple tank farm alarm integration
- Fully compatible with FuelsManager®; tank inventory management made easy
- 8130 RTU and gauge configuration data can be exported to other applications, such as Microsoft Excel® or Access®; document all tank gauge equipment
- Remote configuration of your tank gauges; means less on-tank activities, resulting in less personnel risk
Interface Modules
The 8130 RTU supports up to four modular interface modules. Each module has its own processor for fast and reliable field data scanning. An internal high speed serial data link communicates the data into a central database. The modules make configuration of the internal 8130 RTU database simple and straightforward. Multiple host communication ports provide real-time data to one or multiple host computers.
A range of modules is available for interfacing to nearly any brand of tank gauge equipment or technologies, making it possible to integrate float and tape transmitters, HTG, servo, magnetostrictive and radar gauges. This allows direct gauge communication, making communication protocol converters superfluous, combining all equipment into one tank inventory system.
16 digital I/O channels - 24 VDC, 120 or 240 VAC
- Channels individually configurable for input or output
- Dedicated status LED
- Dedicated fuse for output modules only
Dual high-speed communications channels - Optically isolated
- Up to 32 devices per channel
- Communications with instruments using Rackbus, MODBUS, DDA, TIWAY or CIM protocols
Isolated analog (4-20 mA), Thermocouple, RTD inputs, high speed pulse accumulation or digital I/O channels - 24 VDC, 120 or 240 VAC operation
- Individually configurable for input or output
- Dedicated status LED/fuses
12 bit accuracy A/D with common-mode noise rejection - Dedicated fused 24V line for each channel
- Throughput accuracy (field to database) = ±0.012%.
- Each channel individually configurable for; 4-20 mA loop powered input, 4-20 mA self powered, voltage input
16 Bit accuracy D/A converter - Current or voltage level output (0-24 mA, 0-20 mA, 4-20 mA & 0-5V)
- 8 channels
Dual high-speed communications channels - Optically isolated
- Up to 32 devices per channel
- Communications using TIWAY or CIM protocol
Supports up to 50 tanks - Communicates using Mark/Space protocol
- Interfaces to the Varec 1900 and compatible tank gauge transmitters
20 mA current loop - Up to 15 devices per channel
- Two channels
- Communicates using GPE or Whessoe Bus protocol
Saab TRL/2 Bus - Up to 16 Saab Radar Tank Gauges per channel
- Two channels
Transformer isolated - Up to 10 tanks per channel
- Two channels
- Communications with Enraf tank gauges
Supports up to 50 tanks - Communicates using L&J Tankway protocol
- Interfaces to L&J Tankway compatible tank gauge transmitters
Supports up to 128 tanks - Communicates with LON Series 3500 TCU
- 78 Kbps twisted pair LON interface
Dual high-speed communications channels - RS-232 communications
- Communicates with L&J Model 8100
- Communicates with Veeder Root TLS-350
- Communicates with Universal Sensors & Devices CATLAS
Product Options
Power Supply
- 110/120V AC 50/60Hz
- 220/240V AC 50/60Hz
- 18 - 36 VDC
Host Emulation
- TSU Emulation - for connection to Varec Tank View systems
- CIU Emulation - emulates Enraf model 858 CIU interface
Special Field Communications Options
- Varec Matrix Communication - interfaces to Varec Matrix devices (1600/1700) require 8210, 8201 & 8204 interface modules
- MODBUS Master Communication - using RTU motherboard communications ports
- CIU Communication - interfaces to existing Enraf 858 CIU devices
Calculations & Strapping Tables
- Hybrid tank calculations
- Hydrostatic tank calculations
- Embedded tank strapping tables
Approvals
Accessories
NEMA 4 Enclosures for Class I Division 2 operation
- 24x20x8 in.
- 20x24x8 in. with 48VDC supply
- 24x24x6 in. with 24VDC supply and modem
- 24x20x8 in. with front panel display, no power supply
Miscellaneous Options
- Modem only (specify type)
- Front panel display
8130 RTU I/O Module Options
- DC Output Module 3-60 VDC Normally Open
- AC Input Module 0-140VAC 8mA
- AC Output Module 24-140VAC Normally Open
- DC Input Module 3-32 VDC 18mA
- AC Input Module 90-140 VAC
- AC Output Module 12-140 VAC Normally Open
- DC Input Module 10-32 VDC
- DC Output Module 5-60 VDC Normally Open
- AC Input Module 240 VAC
- AC Output Module 240 VAC Normally Open
- Analog Input Module 4-20mA (use with 8204 only)
- OPTO 22 #G4ODC5R5 Normally Closed
- High Speed Pulse Input Module 1-5 VDC